IEC 60870-5-104: protocol guide / panduan protokol
Start data transfer, interrogate a station and acknowledge counters.
Mulai transfer data, interogasi station, dan akui counter.
Communication walkthrough / Alur komunikasi
- STARTDT act
A controlling station enables data transfer using a U-format control APDU.
Controlling station mengaktifkan transfer data memakai APDU kontrol format U.
- STARTDT con
The controlled station confirms readiness.
Controlled station mengonfirmasi kesiapan.
- General interrogation
An I-format APDU carries C_IC_NA_1 with the interrogation qualifier.
APDU format I membawa C_IC_NA_1 dengan qualifier interogasi.
- Measured value response
Measured data follows activation confirmation; this condensed event shows a scaled tank input.
Data ukur mengikuti konfirmasi aktivasi; event ringkas ini menunjukkan input tangki berskala.
- S-format acknowledgement
The receive sequence acknowledges I-format APDUs, not the process value itself.
Receive sequence mengakui APDU format I, bukan nilai proses itu sendiri.
Source and simulation scope
This is a simplified, deterministic teaching scenario. Timing is illustrative. Messages grouped within one event are explicitly condensed. Hexadecimal fixtures, where shown, contain only the indicated protocol ADU, not a full network capture. No PCAP files are supplied.
IEC 60870-5-104 · technical reference ↗